MOLDED CASE CIRCUIT BREAKERS (MCCB) LS ELECTRIC

MOLDED CASE CIRCUIT BREAKERS (MCCB) LS ELECTRIC

MCCB (Susol and Metasol) LS ELECTRIC can be used for protection in power distribution, motor, and control equipment applications with high breaking capacity and a simple size.


Susol MCCB LS Electric ensures safe and comfortable operation with a wide range of trip units. In addition, it has a simple and sturdy design that depicts the strength of an industrial product.


Metasol MCCB LS ELECTRIC, which meets international standards, has the same size as Metasol ELCB (Earth Leakage Circuit Breaker) LS ELECTRIC. Apart from being able to be used for applications in industry, it can also be used for applications in residential and commercial buildings.


Metasol ELCB (Earth Leakage Circuit Breaker) LS ELECTRIC provides protection against overload, short circuit, and leakage current in accordance with IEC-60947-2 standards.

1.    Susol MCCB LS ELECTRIC 

  • Tipe E-series
    Specification :
    • Application = Power Distribution
    • Current Capacity: 16~1600A
    • Breaking capacity (ICU): 36~150kA @ 380/415VAC
    • Service breaking capacity (Ics): 100%
    • Trip Unit = Adjustable Thermal, Fixed Magnetic Trip Unit (FMU)
    • Ir (A) = 0.8 - 1x In
    • IEC 60947-2 standard
  • Tipe TD100 & TD160 (FMU)
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 16-160 A
    • Breaking Capacity: 50–150 kA (at 380/415 VAC)
    • Ics = 100% x Icu
    • Trip Unit: Adjustable Thermal, Fixed Magnetic Trip Unit (FMU)
    • Ir (A) = 0.8 - 1x In
    • Ii (A) = fixed 400A and 10x In
  • Tipe TS100, TS160 & TS250 (FMU)
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 40-250
    • Breaking Capacity: 50–150 kA (at 380/415 VAC)
    • Ics = 100% x Icu
    • Trip Unit: Adjustable Thermal, Fixed Magnetic Trip Unit (FMU)
    • Ir (A) = 0.8 - 1x In
    • Ii (A) = 10x In
  • Tipe TS400, TS630 & TS800 (FMU)
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 300-800 A
    • Breaking Capacity = 65-150kA (at 380/415 VAC)
    • Ics = 100% x Icu
    • Trip Unit: Adjustable Thermal, Fixed Magnetic Trip Unit (FMU)
    • Ir (A) = 0.8 - 1x In
    • Ii (A) = 10x In
  • Tipe TS160 & TS250 (ATU)
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 125-250 A
    • Breaking Capacity: 50–150 kA (at 380/415 VAC)
    • Ics = 100% x Icu
    • Trip Unit: Adjustable Thermal, adjustable magnetic trip unit (ATU)
    • Ir (A) = 0.8 - 1x In
    • Ii (A) = 5 - 10x In
  • Tipe TS400, TS630 & TS800 (Atu)
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 300-800 A
    • Breaking Capacity = 65-150kA (at 380/415 VAC)
    • Ics = 100% x Icu
    • Trip Unit: Adjustable Thermal, adjustable magnetic trip unit (ATU)
    • Ir (A) = 0.8 - 1x In
    • Ii (A) = 5 - 10x In
  • Tipe TS100, TS160 & TS250 (ETS)
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 40-250 A
    • Breaking Capacity: 50–150 kA (at 380/415 VAC)
    • Ics = 100% x Icu
    • Trip Unit = Electronic Trip Unit Standard Type (ETS)
    • Ir (A) = 0.4 - 1x In
    • Isd (A) = 1.5 - 10x Ir
    • Ii (A) = fixed 11x In
  • Tipe TS400, TS630 & TS800 (ETS)
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 160-800 A
    • Breaking Capacity = 65-150kA (at 380/415 VAC)
    • Ics = 100% x Icu
    • Trip Unit = Electronic Trip Unit Standard Type (ETS)
    • Ir (A) = 0.4 - 1x In
    • Isd (A) = 1.5 - 10x Ir
    • Ii (A) = fixed 11x In
  • Motor Protection Application (MTU)
    Specification :
    • Standard = IEC60947-2
    • Application: Motorcycle Protection
    • Current Capacity = 1.6 - 630 A
    • Breaking Capacity: 50–150 kA (at 380/415 VAC)
    • Ics = 100% x Icu Ë™Trip Unit = Adjustable Magnetic Trip Unit (MTU)
    • Ii (A) = 6 x 12


2.    Metasol MCCB LS ELECTRIC

  • 30AF
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 3–30 A
    • Breaking Capacity = 14-18kA (at 380 VAC) / 10-14kA (at 415 VAC)
    • Ics = 100% x Icu
    • Trip Unit = fixed thermal, fixed magnetic trip units (FTU)
  • 50AF
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 15-50A
    • Breaking Capacity = 18-50kA (at 380 VAC) / 14-50kA (at 415 VAC)
    • Ics = 100% x Icu
    • Trip Unit = fixed thermal, fixed magnetic trip units (FTU)
  • 60AF
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 15-60A
    • Breaking Capacity = 18-22kA (at 380 VAC) / 14-18kA (at 415 VAC)
    • Ics = 100% x Icu
    • Trip Unit = fixed thermal, fixed magnetic trip units (FTU)
  • 100AF
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 15-100A
    • Breaking Capacity = 22kA (at 380 VAC) / 18kA (at 415 VAC)
    • Ics = 100% x Icu
    • Trip Unit = fixed thermal, fixed magnetic trip units (FTU)
  • 125AF
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 15-125A
    • Breaking Capacity = 42-60kA (at 380 VAC) / 37-60kA (at 415 VAC)
    • Ics = 100% x Icu (type S & H)
    • Trip Unit = fixed thermal, fixed magnetic trip units (FTU)
  • 250AF
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 100-250A
    • Breaking Capacity = 30-60kA (at 380 VAC) / 26-60kA (at 415 VAC)
    • Ics = 100% x Icu (type N/S/H)
    • Trip Unit = fixed thermal, fixed magnetic trip units (FTU)
  • 400AF
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 250-400A
    • Breaking Capacity = 42-100kA (at 380 VAC) / 37-85kA (at 415 VAC)
    • Ics = 100% x Icu (type N/S/H)
    • Trip Unit = fixed thermal, fixed magnetic trip units (FTU)
  • 800AF
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 500-800A
    • Breaking Capacity = 45-100kA (at 380 VAC) / 37-85kA (at 415 VAC)
    • Ics = 100% x Icu (type N & S)
    • Trip Unit = fixed thermal, fixed magnetic trip units (FTU)
  • 1000AF & 1200AF
    Specification :
    • Standard = IEC60947-2
    • Application: Power Distribution
    • Current Capacity: 1000-1200A
    • Breaking Capacity = 65-85kA (at 380 VAC) / 65-85kA (at 415 VAC)
    • Ics = 100% x Icu 
    • Trip Unit = fixed thermal, fixed magnetic trip units (FTU)