NDM1 NADER SERIES MCB

NDM1 NADER SERIES MCB
  1. Product Overview

 

Product Model

NDM1-63

NDM1-125

NDM1T-63

Rated Voltage

AC230/240V(1P),

AC400V(2P, 3P, 4P)

DC80V(1P, 2P)

AC230/240V,

AC400/415V(2P, 3P, 4P)

DC60/80(1P)

DC80/125V(2P)

AC230/240V

AC400/415V(2P, 3P, 4P)

Rated Current

1A, 2A, 3A, 4A, 5A, 6A, 10A, 20A, 25A, 32A, 40A, 50A, 63A

50A, 63A, 80A, 100A, 125A

1A, 2A, 3A, 4A, 5A, 6A, 10A, 20A, 25A, 32A, 40A, 50A, 63A

Number of Poles

1P, 2P, 3P, 4P

1P, 2P, 3P, 4P

1P, 2P, 3P, 4P

Certificate

CCC

CCC, CE, TUV, UL1077

CCC, CE, TUV

 

  1. Product Features
  • Application Scope

NDM1 series miniature circuit breaker is used in low-voltage terminal distribution for industry, civil building, energy, telecommunication and construction to do protection from short circuit and overload, to control, to disconnect and protect DC systems.

  • Design Features
  • Full protection functions: Have protective device for short circuit and overload.
  • Connection is safety and reliable: Use “Frame” connection structure.
  • Easily function expansion: many accessory, such as: residual current operated release, auxiliary contact, alarm contact and bus-bar can match this product.
  • Modularized and series match.
  • Easily mounting: TH35 standard mounting rail.

 

  • Structure Features
  • NDM1-63/ NDM1T-63 External Structure Diagram

 1 : Line

2 : Load

3 : Operating Handle

4 : Assembly Interface

  • NDM1-125 External Structure Diagram

1 : Line

2 : Switching-Closing Indicator

3: Load

4 : Operating Handle

5 : Assembly Interface

  • Standards
  • NDM1-63 Standards
  1. GB 10963.1-2005 Electric accessory – Over current protective circuit breaker is used in home or similar sites. First Part: Circuit Breaker for AC.
  2. IEC 60898-1:2002 Electrical accessories-Circuit-breakers for overcurrent protection for house hold and similar installation-Part 1: Circuit-breakers for a.c.operation.
  • NDM1T-63 and NDM1-125 Standard
  1. GB 14048.2 Low-voltage switchgear and control-gear equipment, Second Part: Circuit Breaker.
  2. IEC 60947-2 Low-voltage switchgear and controlgear-Part 2: Circuit-breakers.
  1. Working Condition
  • Electrical Symbol
  • Applicable Condition
     
    • Ambient Usage Temperature and Storage Temperature
      Ambient Usage Temperature: -350C~+700C, Standard Temperature: +300C, correction factor of different ambient usage temperature refer to sheet 1.
      Storage Temperature: -400C~+700C
    • Altitude
      The altitude of the mounting site ≤2000m.
    • Relative Usage Humidity and Relative Storage Humidity
      The relative humidity shouldn’t exceed 50% when the ambient air temperature is +40 degrees, higher humidity can be allowed in lower temperature. For example, the humidity can be 90% when the ambient temperature is +20 degrees. Necessary measures should be acted for the condensation produced by the changed temperature.
  • Pollution Degree

3

  • Protection Level

Level of Product Protection: IP20

  • Mounting Method

Mounted on TH35mm x 7.5 Standard Rail.

  • Mounting Direction
  • Vertical Mounting: The inclination between mounting plane and vertical plane should ≤ + 5 degrees
  • Horizontal Mounting
  • Environmental Requirement

Comply with RoHS

  1. Product Technical Characteristic
  • Model and implication

No.

Implication

                       Instruction

1

Brand Code

ND: Nader

2

Product Code

M: Miniature Circuit Breaker

3

Design Code

1

4

Product Standards

GB 10963.1 ,

IEC 60898-1

GB 14048.2 ,

IEC 60947-2

GB 14048.2 ,

IEC 60947-2

5

Frame Rating (A)

63A

125A

63A

6

Instantaneous Tripping Characteristic

B: Instantaneous Tripping Range 3ln ~ 5ln;

C: Instantaneous Tripping Range 5ln ~ 10ln;

D: Instantaneous Tripping Range 10ln ~ 14ln;

C: Instantaneous Tripping Range 8ln(1 ± 20%);

D: Instantaneous Tripping Range 8ln(1 ± 20%);

 

B: Instantaneous Tripping Range 4ln(1 ± 20%);

C: Instantaneous Tripping Range 8ln(1 ± 20%);

D: Instantaneous Tripping Range 12ln(1 ± 20%);

7

Rated Current

1A, 2A, 3A, 4A, 5A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A

50A, 63A, 80A, 100A, 125A

1A, 2A, 3A, 4A, 5A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A

8

Number of Poles

1P, 2P, 3P, 4P

1P, 2P, 3P, 4P

1P, 2P, 3P, 4P